Two injured in Arc Flash event

Two employees of the Cuyahoga Falls Electric System were injured in an arc flash incident that occurred while working on customer premises and on customer’s equipment.

Both employees were transported to a burn unit but it has been reported that both workers were “doing okay… they’re conscious and talking.”

City officials said that out of concern for the privacy of employees and their families, the city will not release the names or current conditions of the employees without their permission.

The electric department is one of nine city departments employing more than 300 public service workers.

According to the department’s website, the city has been providing residents and businesses with the benefits of public power through the Cuyahoga Falls Electric System since 1888 according to the department’s website.

Make sure your company provides qualified persons training (employees who will perform energized work on equipment) with skills and knowledge to perform their job safely. Meets requirements of NFPA 70E, Article 110.6 and OSHA 29CFR1910.332.

Arc Testing of Foam Lined Hard Hats

Oberon Arc Testing at Kinetrics Lab, April 30, 2010

ASTM Committee F18 on Electrical Protective Equipment for Workers is developing a new arc exposure test method for hard hats in part due to concerns in the industry that the foam inside insulated hard hats can melt and/or ignite. Recently, Oberon has conducted arc tests on Type 2, Class E hard hats with foam liners. For arc flash protection, hard hats are worn with an arc rated face shield or an arc rated hood with a shield window. In the NFPA 70E Hazard/Risk Categories (HRC) 1, 2 and 2-star designated for incident energy levels from 1.2 to 8 cal/cm2, hard hats are equipped with an arc rated face shield. For HRC3 and HRC4, designated for incident energies above 8 cal/cm2 and up to 40 cal/cm2, arc rated hoods are required. Within the utility industry which is excluded from the NFPA 70E standard, hard hats can be directly exposed well above an incident energy of 8 cal/cm2 when used with a balaclava hood and an arc rated faceshields or arc rated goggles. The intent of these Oberon tests was to conduct arc exposures in the range of 25 cal/cm2 with and without an arc rated face shield protecting the hard hat liner.

In test 10-1861A, the hard hats/face shield assembly was initially mounted facing the arc exposure in the standard configuration for the ASTM F2178 test method for face protective products. The hard hat was labeled “Dynamic HP542 hardhat with foam liner, made in Canada, CSA Z94.1-05 & ANSI Z89.1-2009, Type 2, Class E, Size 53-64 cm, 65/8-8, HPDE” and was equipped with an Oberon ARCX 12 cal shield. As expected, the face shield protected the hard hat and liner. There was no after-flame from the hard hat or liner and no melting, dripping or damage to the hard hat or liner. Figure 1 shows the inside of the hard hat after the exposure of 27.8 cal/cm2.

In test 10-1862, two hard hats/face shield assemblies were mounted backwards on the mannequin head so that the back sides of the two hard hats were facing the arc exposure. In Figure 2, position A is shown with a hard hat labeled “North A89/A89R hardhat with foam liner, SEI Cert. Mod. CSA Z94.1-05 & ANSI/ISEA Z89.1-2009, Type 2, Class E, Size 53-64 cm, 65/8-8, HPDE” equipped with an ARCX 12 cal shield mounted backwards. In position B, the same hard hat and face shield used for test 10- 1861 was exposed a seconds time but with the back of the hard hat facing the arc exposure. In this orientation, the face shield does not protect the hard hat and liner. However, there was no after-flame from the hard hat or liner and no melting, dripping or damage to the hard hat or liner with an incident energy exposure on position A of 27.0 cal/cm2 and on position B 23.3 cal/cm2.

Certainly at some level of arc flash exposure, a hard hat and liner can exhibit ignition, melting and dripping. The ASTM F18 Committee test method development will determine the exposure level at which these phenomena can be initiated. Based on this limited testing, it appears that that ignition, melting and dripping are not initiated at exposures up to approximately 25 cal/cm2.

I Know the Voltage, What Arc Suit Should I Get???

Voltage Does Not Determine Hazard Category Levels !

Knowing the voltage is only one piece of determining Arc Flash PPE. The available fault current (amps), the working distance between the worker and the equipment, the clearing time of the circuit protection device, the spacing between conductors or from a conductor to ground, the number of phases, whether the conductors are in an en- closure, and the equipment configuration are also needed to determining the potential Arc Flash exposure level and the required PPE.

NFPA 70E Table 130.7(C)(9)(a) is organized by system voltage level, but at each voltage or range of voltages, there are several different levels of PPE based on the type of task and the equipment as well as on footnote information for fault current and clearing time. For example, a 600 volts system could have a hazard level ranging from Hazard Risk Category (HRC) 0 (PPE up to 2 cal/cm cm2) to HRC 3 (PPE up to 25 cal/cm2) depending the task, the type of equipment and the footnote information on fault current available and clearing time.

The bottom line is that you can’t rely on voltage alone to figure out what arc flash protection you need. You’ll need to know all the factors noted above and conduct a hazard analysis to determine the potential arc exposure level. In lieu of a formal hazard analysis, you could use NFPA 70E Table 130.7(C)(9)(a) to determine the hazard risk category and Table 130.7(C)(10) to determine the PPE needed for the task. Contact Us and we will help you quickly select the appropriate protective clothing for the tasks listed in the NFPA 70E Table 130.7(C)(9)(a).

Shrapnel Hazard Ballistic Testing Report

Introduction: Over the past several years, personal protective equipment (PPE) has been developed to protect workers from the intense heat energy of an electric arc flash event. Oberon arc flash suits including hoods and hood shield windows are available with heat protection levels up to 100 cal/cm2. However, there is increasing concern among some members of the NFPA 70E Technical Committee regarding potential hazards other than heat exposure that are also part of an electric arc event, e.g. shrapnel, pressure waves and high sound levels. The NFPA 70E Technical Committee elected to limit its Hazard/Risk Category exposure levels to 40 cal/cm2 in the proposed 2004 edition until a better understanding of these additional arc flash hazards is achieved. Oberon and DuPont have conducted limited ballistic testing for the better understand the performance of Oberon arc flash product performance against shrapnel hazards.

Description of the Arc Flash Event: An electric arc flash event consists of a complicated series of hazards primarily originating from the nearly instantaneous generation of an atmospheric plasma. These hazards include a radiant heat exposure, a pressure or “shock” wave, an excessive noise exposure, molten metal splatter (from the plasma erosion of the conductors and nearby materials), and ejection of projectiles or bits of “shrapnel” accelerated by the explosive force of the plasma formation.

Shrapnel Generation in an Arc Flash Event: There is anecdotal evidence that electrical workers have been injured by projectiles or shrapnel emitted from an arc flash event. The nature of the shrapnel hazard has not been quantified or related to arc flash parameters, and it is likely that the projectile mass, shape and velocity of shrapnel emitted from an arc event is dependent on the type of equipment involved, the failure mode, and the energy available. It seems logical that the same parameter that has primary influence on the pressure wave, i.e., the arc current level, would be expected to influence the energy available to accelerate shrapnel to ballistic velocities. There may also be an influence from the electro-magnetic fields acting on the projectile.

Shrapnel Hazard Versus Heat Exposure in an Arc Flash Event: Because the shrapnel hazard is very likely related to fault current and the explosive forces during the first half cycle of an arc flash event, and heat exposure is related to both fault current and the duration of the arc flash, the hazard analysis used for heat exposure cannot be applied to the shrapnel hazard. For instance, it is possible to have a very short arc flash duration of a half cycle but with a high fault current of 100kA that could generate a shrapnel hazard, but these arc parameters would create a relatively low heat exposure. Conversely, we could have a long duration arc flash event of 60 cycles (1 second) with a low fault current of 8kA that would be much less likely to produce a significant shrapnel hazard but would create a very high heat exposure. Consequently, the shrapnel hazard cannot “piggyback onto the hazard analysis used for heat exposure.

Testing Oberon PPE Against the Shrapnel Hazard: Although it is not possible to accurately quantify the shrapnel hazard, i.e. we can’t predict the projectile mass, shape, temperature, and velocity for each potential arc flash event, it is possible to measure the shrapnel or ballistic resistance of arc flash fabric systems and hood shield windows to standardized ballistic threats. Oberon has utilized standard fragment testing technology developed to evaluate body armor and helmets for military personnel to evaluate Oberon arc flash protective products. Competitive arc flash PPE suppliers, at this point in time, have not performed ballistic testing of their arc flash PPE.

Arc flash hood windows and face shields must meet the projectile impact requirements of ANSI Z87.1. This standard specifies that a 0.25 inch steel ball projectile must not penetrate the shield window or face shield at a velocity of 300 feet/second. It does not consider irregularly shaped projectiles or ballistic velocities (generally considered to start at approximately 500 to 600 feet/second) that may accompany an arc flash event. Ballistic testing is usually conducted using two different projectiles: bullets that, in most cases, do not have sharp edges, and fragments that generally do have sharp edges. Since projectiles emitted from an arc flash event would tend to be irregular in shape and likely to have sharp edges, testing of arc flash PPE was conducted using fragments instead of bullets.

Table 1 provides ballistic test results for 100 cal/cm2 rated hood shield windows. Each hood shield window was molded from polycarbonate material. Ballistic V50 results are provided for a test fragment diameter of 0.22 inches. V50 is the velocity at which 50% of the projectiles penetrate the target specimen.

Table 1: Ballistic V50 Results Hood Shield Windows

100 cal/cm2 Arc Rated Hood Shield Window Specimen Fragment Caliber or Diameter inches V50 feet/second
Arc Rated Polycarbonate Window 0.22 377
Arc Rated Polycarbonate with Clear Polycarbonate Backup Window 0.22 856

Table 2 provides ballistic test results for the Oberon ARC100 and ARC100B inherently FR fabric systems and a competitive Flame Retardant Treated (FRT) cotton fabric system with an arc rating of 100 cal/cm2. Ballistic V50 results are provided for a test fragment caliber (diameter) of 0.22 and 0.308 inches. These V50 results illustrate the expected benefit due to the additional,    tightly    woven,    Kevlar®    para-aramid “ballistic” fabric layer in the ARC100B system. Even though the competitive FRT cotton arc flash suit fabric system is more than 60% heavier than the standard ARC100 fabrics system, the competitive FRT fabric system provides less ballistic protection than the standard Oberon ARC100 fabric system. The poorer showing of the much heavier FRT cotton specimen is expected due to the significantly lower fabric tensile strength of FRT cotton compared to the inherently FR Oberon materials.

Table 2. Ballistic V50 Results for Arc Rated Fabric Systems

100 cal/cm2 Arc Rated Layer Fabric System Specimen Fabric System Weight (oz/yd2) V50 feet/second(Fragment Caliber/Diam. inches)
ARC100B System withKevlar® Ballistic Layer 27 789 (0.308)
ARC100 Fabric System No Ballistic Layer 26 627 (0.308)
Flame Retardant Treated Cotton No Ballistic Layer 42 610 (0.22)
ARC100 Fabric System No Ballistic Layer 26 690 (0.22)

US Department of Labor’s OSHA cites Grenada, Miss., plant for amputation hazards and other safety violations, proposes more than $113,000 in fines

GRENADA, Miss. – The U.S. Department of Labor’s Occupational Safety and Health Administration has cited Grenada Stamping and Assembly Inc., doing business as Ice Industries Grenada, for 26 safety violations carrying proposed fines of $113,400. In April, OSHA officials opened an inspection at the facility under the agency’s national emphasis program on amputations after learning of a work-related amputation.

Twenty-four serious violations involve failing to properly install guards on machinery to prevent workers from becoming injured by the equipment, as well as electrical hazards, defective slings in use, a defective powered industrial truck that had not been removed from operations, fall hazards and improperly installed exit doors lacking signage. A serious violation occurs when there is substantial probability that death or serious physical harm could result from a hazard about which the employer…Read More

US Labor Department’s OSHA cites Houston, Texas–based construction company for electrical, fall and other hazards at Little Rock, Ark., work site

LITTLE ROCK, Ark. – The U.S. Department of Labor’s Occupational Safety and Health Administration has cited Houston, Texas–based Atlas Texas Construction and Trading Inc. for 11 serious safety violations carrying proposed penalties of $51,000.

OSHA’s inspection, initiated under a national emphasis program on construction, found that about 20 workers were exposed to electrical and fall hazards while constructing the Lisa Academy School on Corporate Hill Drive in Little Rock.

“This company disregarded the safety of its workers by exposing them to multiple hazards,” said Carlos Reynolds, director of OSHA’s Little Rock Area Office, which conducted the inspection. “OSHA’s standards must be followed to prevent injuries and fatalities.”

The violations involve failing to train workers on the hazards of electrical equipment…Read More